Customer Bill of Materials

Submitted by: Submitted by

Views: 71

Words: 1585

Pages: 7

Category: Business and Industry

Date Submitted: 12/01/2014 07:05 AM

Report This Essay

1 PRLC Switchboard

Pow-R-Line C Switchboard, Front Access/ Front and Rear Align, Type 1

480Y/277V 3-Phase 4-Wire, 1600 Copper, Minimum Interrupt Rating: 65kA, Bus Bracing Rating: 65kA

1 Pow-R-Line C

2 Vertical Isol. Barrier

2 Horizontal Isol. Barrier

1 Service Entrance Label

1 1600 Amp CU Distribution Structure

13 Thermal Mag Trip - Standard

1 1600 Amp CU Main Structure

1 Bottom Fed Switch

1 Ground fault protection

3 400A 3P [HKD 400A Frame], Trip 400 A., Thermal Mag, (1) 2/0-500 kcmil, Mechanical

3 25A 3P [HFD 225A Frame], Trip 25 A., Thermal Mag, #14-1/0, Mechanical

4 70A 3P [HFD 225A Frame], Trip 70 A., Thermal Mag, #14-1/0, Mechanical

1 100A 3P [HFD 225A Frame], Trip 100 A., Thermal Mag, #14-1/0, Mechanical

1 90A 3P [HFD 225A Frame], Trip 90 A., Thermal Mag, #14-1/0, Mechanical

1 60A 3P [HFD 225A Frame], Trip 60 A., Thermal Mag, #14-1/0, Mechanical

1 1600A 3 Pole Bolted Pressure Switch, Class L fuse clips provided, (fuses provided by others), (5) #4-500 kcmil, Mechanical, B

Designations:

1 Dry Type Transformer

CUSTOM TRANSFORMERS MUST BE APPROVED BY TRC - Avery Creek

This is a custom manufactured product. Once it is released for manufacturing it cannot be canceled. This product cannot be returned for credit.

Custom Transformer, Style Number V48M28B75AFEE

Similar To Standard Transformer V48M28T75EE

Transformer Type: General Purpose Vented

3 PHASE, 75 KVA, 480 Primary Volts, 208Y/120 Secondary Volts,

80C Temperature Rise, Aluminum Winding Material, NEMA 2 (N3R w/opt'l weathershield) Enclosure Type, 60 HZ

Customized Values:

CUSTOM: Anti-Fungus Protection: Y

CUSTOM: Temperature Rise: 80C

CUSTOM: Sound Reduction: 3

Standard Values

K-Factor: 1

TAPS: 2@+2.5%, 4@-2.5%

NEMA ST20 Sound Level: 50

Nema TP-1 Energy Efficient: Y

Infrared Viewing Window: None...