Technical Note – Kingfisher RTU Modbus Interface
September 12, 2003 – Rev. A
©Copyright InduSoft Systems Ltd. 2003
Kingfisher RTU Modbus Interface
Kingfisher RTU Configuration to Support
the Standard Modbus Serial Protocol
Introduction
Kingfisher RTU can be configured to behave as a Modbus Slave device. InduSoft Web Studio (IWS) provides the
MODBU driver, which implements the Modbus Master protocol. Therefore, after following the instructions described in
this document to configure the Kingfisher RTU device, IWS is able to exchange data with the device via Modbus serial
protocol.
Note: Information in this document, such as URLs, may no longer be valid on the date that this
document is being read.
Configuring Kingfisher RTU
The Kingfisher RTU can be configured with the Kingfisher Toolbox utility, supplied by Kingfisher. Before configuring the
device as a Modbus Slave, make sure you have the modbu.32 file. This file is available for download at the following
URL: http://www.rtunet.com/noframe/c-supp2.htm.
Note: Click on the CP-10/11 Firmware and Driver from the URL mentioned previously and enter a valid
User Name and Password to access the file. Consult Kingfisher if you have any problem accessing this
file.
Follow the steps below to configure the Kingfisher RTU to perform as a Modbus Slave device:
1. Install and Run the Kingfisher Toolbox utility software.
2. Select the Utilities → Advanced → Download Firmware Driver menu.
3. Select the modbus.32 file from the \KingfisherRTU\Drivers\ folder.
Page 1
Technical Note – Kingfisher RTU Modbus Interface
September 12, 2003 – Rev. A
©Copyright InduSoft Systems Ltd. 2003
4. Create a new SDB (Site Database) file by the File → New menu. The SDB file contains the settings settings, such
as RTU number, name, port list, network list, and so forth.
5. Select the Configuration → Address & Description menu and set the Site Address to 1.
6. Select the Configuration → Port List menu and...