Liquid line sizing
50 feet liquid line + 200 feet estimated equivalent length = 250 feet
115 condensing temp – 180F subcooling= 97oF
400F evap temp
System load 60 tons
Interpolation correction factor
95 - .95
100 - .98
Change in temp=5 – Change in cap=.03
.03÷5=.006 Correction factor =.96
60 tons x .96 correction factor= 57.6 tons
250 feet, 57.6tons= 11/8
11/8 would not be good because the gas velocity is way above 4000
Suction line
20 feet
97 condensing
40 evap
60 ton system load
Interpolation correction factor
95 – 1.03
100 – 1.01
Change in temp=5 Change in cap=.02
.004÷5=.004 correction factor=1.022
60tons x 1.022= 61.32
20feet, 61.32tons=31/8
This is a good size because the gas velocity is about 2500
15 feet double riser
3 short radius elbows x 8.0= 24
1 line tee x 5.4=5.4
2 long radius elbows x 5.1=10.2
54.6 feet
54.6 feet, 61.32=31/8
This is a good size because the gas velocity is about 2500
Discharge line
15 feet
Interpolation correction factor
95 – 1.04
100- 1.02
Change in temp=5 Change in cap=.02
0.02÷5=1.048
60tons x 1.048=62.88
15feet, 62.88=21/8
21/8 is a good size because the didcharge gas velocity is about 2500
8 feet double riser
2 short radius elbows 5.2= 10.4 feet
2 long radius elbows 3.4 6.8
25.2
62.88 tons, 25.2 feet 21/8
21/8 is a good size because the didcharge gas velocity is about 2500
2
10tons
Condensing temp 1000F==223.94
Suction temp 400F
Psia at valve inlet
104 - 222.42
106 – 228.50
Change in temp=4 change inpsia =6.08
6.08÷4=1.52
Psia=223.94
Less psi drop in liquid line=2
Less loss of head due to 20 feet hight=9.9
Psia at inlet+212.04
Psia at valveoutlet
400F suction temp at compressor=83.206
Plus pressure drop at suction line=2
Plus pressure drop across coil and distributor=20
Psia at valve outlet=...